The safest way to calibrate fieldbus instruments

AMS Instrumentation & Calibration Pty Ltd
Thursday, 14 January, 2010


Fieldbus is becoming more and more common in today’s instrumentation. Fieldbus transmitters must also be calibrated just like conventional instruments, and there are also industrial environments where the calibration of fieldbus instruments should not only be made accurately and efficiently, but also safely.

When safety becomes a top priority issue in calibration, intrinsically safe fieldbus calibrators enter into the picture.

Conventional transmitters can deliver only one simultaneous parameter, one way. Each transmitter needs a dedicated pair of cables, and I/O subsystems are required to convert the analog mA signal to a digital format for a control system.

Fieldbus transmitters are able to deliver a huge amount of information via the quick two-way bus. Several transmitters can be connected to the same pair of wires, so conventional I/O systems are no longer needed because segment controllers connect the instrument segments to the quicker, higher-level fieldbus backbone. Being an open standard, instruments from any manufacturer can be connected to the same fieldbus.

Currently, a large number of fieldbus installations already exist and the number is quickly increasing. A large portion of new projects are currently being carried out using fieldbus, and critical applications and hazardous areas have also begun to adopt fieldbus.

The Foundation Fieldbus and Profibus systems have begun to clearly dominate the fieldbus markets. Both Foundation Fieldbus and Profibus have reached such a large market share that both buses will most likely remain in the future.

The development of new fieldbuses has slowed down and it is unlikely that new fieldbus standards will appear in the near future to challenge the position of Foundation Fieldbus or Profibus. Recent cooperation between Foundation Fieldbus and Profibus suppliers will further strengthen the position of these two standards.

Fieldbus benefits for industry

Obviously process plants would not start utilising fieldbus if it would not offer them benefits compared to alternative systems. One important reason is the better return on investment. Although fieldbus hardware may cost the same as previous technologies, or even a little bit more, the total installation costs for fieldbus are far less. There are many reasons for this, such as reduction in field wiring, lower installation labour cost, reduced planning costs, and no need for conventional I/O subsystems.

Another advantage is the online self-diagnostics that helps in predictive maintenance and eventually reduce downtime, offering maintenance savings. Remote configuration also helps to support reduced downtime. The improved system performance is an important criterion for some plants.

Fieldbus transmitters must also be calibrated

The main difference between a fieldbus transmitter for pressure or temperature and conventional or HART transmitters is that the output signal is a fully digital fieldbus signal.

The other parts of a fieldbus transmitter, however, are mainly comparable to conventional or HART transmitters. Although modern fieldbus transmitters have been improved compared to older transmitter models, this does not eliminate the need for calibration. There are also many other reasons, such as quality systems and regulations that make periodic calibration compulsory.

Calibrating fieldbus transmitters

The word ‘calibration’ is often misused in fieldbus terminology compared to the meaning of the word in metrology. In fieldbus terminology, ‘calibration’ is often used to mean the configuration of a transmitter. In terminology pertaining to metrology, ‘calibration’ means that you compare the transmitter to a traceable measurement standard and document the results. So it is not possible to calibrate a fieldbus transmitter using only a configurator or configuration software. Also, it is not possible to calibrate a fieldbus transmitter remotely.

Fieldbus transmitters are calibrated in very much the same way as conventional transmitters - you need to place a physical input into the transmitter and simultaneously read the transmitter output to see that it is measuring correctly. The input is measured with a traceable calibrator, but you also need to have a way to read the output of the fieldbus transmitter. Reading the digital output is not always an easy thing to do. When fieldbus is up and running, you can have one person in the field to provide and measure the transmitter input while another person is in the control room reading the output. Naturally, these two people need to communicate with each other in order to perform and document the calibration.

While your fieldbus and process automation systems are idle, you need to find other ways to read the transmitter’s output. In some cases you can use a portable fieldbus communicator or a laptop computer with dedicated software and hardware.

Until recently, no practical way to calibrate fieldbus transmitters has existed. A modern fieldbus calibrator is a combination of a multifunction process calibrator and a fieldbus configurator. With such a calibrator you can calibrate a fieldbus pressure and temperature transmitter, as the calibrator can simultaneously generate and measure the transmitter input and also read the digital fieldbus output of the transmitter. A modern fieldbus calibrator can also be used to change the configuration of a fieldbus transmitter. If you find that the fieldbus transmitter fails in calibration, you can also use the calibrator to adjust the fieldbus transmitter to measure correctly. Using a documenting calibrator will also mean that the fieldbus calibrator will automatically document the calibration results in its memory, from where the results can be uploaded to calibration software. This eliminates the time-consuming and error-prone need for manual documenting using traditional methods.

When looking for a fieldbus calibrator, search for a compact, easy-to-use and field-compatible calibration solution. The calibrator should at least calibrate Foundation Fieldbus H1 or Profibus PA transmitters, which are the most common applications.

The most important advantage of a fieldbus calibrator is its possibility to calibrate, configure and trim the Foundation Fieldbus H1 or the Profibus PA transmitters using a single unit; and calibration can be performed by one person instead of two.

What is intrinsically safe calibration?

By definition, intrinsic safety (IS) is a protection technique for safely operating electronic equipment in explosive environments. The concept has been developed for safely operating process control instrumentation in hazardous areas. The idea behind intrinsic safety is to make sure that the available electrical and thermal energy in a system is always low enough that ignition of the hazardous atmosphere cannot occur. A hazardous atmosphere is an area that contains elements that may cause an explosion: a source of ignition, a flammable substance and oxygen.

Hazardous area classifications in IEC/European countries are:

  • Zone 0: An explosive gas and air mixture is continuously present or present for a long time.
  • Zone 1: An explosive gas and air mixture is likely to occur in normal operation.
  • Zone 2: An explosive gas and air mixture is not likely to occur in normal operation, and if it occurs it will exist only for a short time.

An intrinsically safe calibrator is therefore designed to be incapable of causing ignition in the surrounding environment with flammable materials, such as gases, mists, vapours or combustible dust. Intrinsically safe calibrators are also often referred to as being ‘Ex calibrators’, ‘calibrators for Ex Areas’, or ‘IS calibrators’. An Ex Area also refers to an explosive environment and an Ex calibrator is a device designed for use in the type of environment in question.

Where is intrinsically safe calibration required?

Many industries require intrinsically safe calibration equipment. Intrinsically safe calibrators are designed for potentially explosive environments, such as oil refineries, rigs and processing plants, gas pipelines and distribution centres, petrochemical and chemical plants, as well as pharmaceutical plants. Basically, any potentially explosive industrial environment can benefit from using intrinsically safe calibrators.

What are the benefits of using intrinsically safe calibrators?

There are clear benefits in using intrinsically safe calibration equipment. First of all, it is the safest possible technique. Secondly, the calibrators provide performance and functionality.

Safest possible technique

Intrinsically safe calibrators are safe for employees, as they can be safely used in environments where the risk of an explosion exists. In addition, intrinsically safe calibrators are the only technique permitted for Zone 0 environments.

Performance and functionality

Multifunctional intrinsically safe calibrators provide the functionality and performance of regular industrial calibration devices, but in a safe way. They can be used for calibration of pressure, temperature and electrical signals. A documenting intrinsically safe calibrator, such as the Beamex MC5-IS, provides additional efficiency improvements with communication with calibration software. This eliminates the need for manual recording of calibration data and improves the quality and productivity of the entire calibration process.

Are intrinsically safe calibrators technically different from regular industrial calibrators?

Intrinsically safe calibrators are different from other industrial calibrators in both design and technical features. In view of safety, there are also some guidelines and constraints for how to use them in hazardous areas. Every intrinsically safe calibrator is delivered with a product safety note, which should be read carefully before using the device. The product safety note lists all the ‘do’s and don’ts’ for safe calibration.

The differences in design and technical features were made with one purpose in mind - to ensure that the device is safe to use and is unable to cause an ignition. Typical differences that make an intrinsically safe calibrator unable to cause ignition are:

  • The outer surface is made of conductive material.
  • There are constraints in using the device (listed in the Product Safety Note).
  • There are some differences in available electrical ranges (for example, the maximum is lower).
  • The battery is slower to charge and quicker to discharge.
  • The battery must be charged in a non-Ex area.
  • When using external pressure modules, they must also be IS versions.

What are ATEX and IECEx?

ATEX (‘ATmosphères EXplosibles’) is a standard set in the European Union for explosion protection in industry. ATEX 95 equipment directive 94/9/EC concerns equipment intended for use in potentially explosive areas. Companies in the EU where the risk of explosion is evident must also use the ATEX guidelines for protecting the employees. In addition, the ATEX rules are obligatory for electronic and electrical equipment that will be used in potentially explosive atmospheres sold in the EU as of 1 July 2003.

The IEC (International Electrotechnical Commission) is a non-profit international standards organisation that prepares and publishes international standards for electrical technologies. The IEC TC/31 technical committee deals with the standards related to equipment for explosive atmospheres, and IECEx is an international scheme for certifying procedures for equipment designed for use in explosive atmospheres. The objective of the IECEx Scheme is to facilitate international trade in equipment and services for use in explosive atmospheres, while maintaining the required level of safety.

Is service different for intrinsically safe calibrators?

There are certain aspects that need special attention when doing service or repair on an intrinsically safe calibrator. The most important thing to remember is that an intrinsically safe calibrator must maintain its intrinsic safety after the service or repair. The best way to do this is to send it to the manufacturer or to an authorised service company for repair. Recalibration can be done by calibration laboratories (still preferably with ISO/IEC 17025 accreditation).

AMS Instrumentation & Calibration Pty Ltd
www.ams-ic.com.au
Beamex
www.beamex.com
 

Related Articles

Sampling gases and volatile liquids: essential strategies

Following gas sampling best practices can improve product output and reduce fugitive emissions.

Planetary gearbox supports global success of composting solution

New Zealand company Global Composting Solutions is having international success with its...

5 things to consider before implementing a UPS

UPS systems play a vital role in the health of your control cabinet: consider these five things...


  • All content Copyright © 2024 Westwick-Farrow Pty Ltd